Technical Information

Technical Information To TOP

Panel Cooling Units

Series Top

Method for selecting heat exchanger for panel

Indoor type heat exchanger required rated capacity

Estimated heat generation quantity inside panel (W) ÷{desired set temperature inside panel (°C) -highest surrounding temperature (°C)} – control panel effective surface area (m2) x thermal conductivity ( 5.0W/m2・K )

*Thermal conductivity is generally 5.0 ~ 6.0 in case of general control panel.

Outdoor type heat exchanger required rated capacity

{Estimated heat generation quantity inside panel (W) + penetrated heat quantity (W)} *÷{desired set temperature inside panel (°C) -highest surrounding temperature (°C)} - control panel effective surface area (m2) x thermal conductivity ( 5.0W/m2・K )

*Penetrated heat quantity is the total of heat penetrated from ceiling outside the room and from side surface.

*Thermal conductivity is generally 5.0 ~ 6.0 in case of general control panel.

Product SearchYou can search by series and make