1300/1400
Head(m)
14/20
PCU Series
Cooling capacity (W) | 5400/6000 |
---|---|
Heating capacity (W) | 1200 / 1600 |
Circulating water temperature range (℃) | 5 to 40 |
Temperature stability (℃) | ±0.1 |
Circulating water rated flow rate (ℓ/min) | 30/35 |
(50 / 60Hz)
Cooling scheme | Air-cooling type |
---|---|
Cooling capacity (W) *1 | 5400 / 6000 |
Heating capacity (W) *1 | 1200 / 1600 |
Circulated water *2 | Clean water, Ethylene glycol solution (concentration 15 wt% or less), Propylene glycol solution (concentration 15 wt% or less) |
Circulating water temperature range (℃) | 5 to 40 |
Temperature stability (℃)*3 | ±0.1 |
Use Area Temperature (℃) | 5~45 |
Circulating water rated flow rate (ℓ/min) | 30/35 |
Maximum discharge pump head (m) *4 | 34/48 |
Tank capacity (ℓ) | Approx. 12 |
Dimensions (mm) *5 | H997×W400×D600 |
Coating Color | Munsell N-87 |
Weight (kg) | Approx. 87 |
Casters (Φmm×unit) | 50×4 |
Rated Voltage (V) *6 | 3-phase 200 VAC / 200~220 |
Power Consumption (kW) *1 | 2.3 / 3.0 |
Current consumption (A) *1 | 10.2 / 10.2 |
Recommended breaker capacity (A) | 30 |
Circulating water inlet / outlet port size | Rc3/4 |
Drain discharge port size | G1/2 |
Components / Compressor | Fully sealed rotary type |
Components / Condenser | Parallel flow condenser type |
Components / Evaporator | Structure : Plate-type heat exchanger Material : SUS316 (copper brazing) |
Components / Circulating pump | Structure : Multi-stage centrifugal pump Output : 0.43/0.74 (kW) |
Refrigerator | R1234yf 725g |
Noise (dB) *7 | 63 / 65 |
Safety circuit / Compressor | Thermal protector, Electromagnetic switch |
Safety circuit/Pump | Electromagnetic switch |
Safety circuit / Fan motor | Thermal protector, Current fuse |
Input / Alarm output | No voltage open-contact (Max. AC250V/1A, DC30V/2A) |
Input/Output / Water temperature upper/lower limit output | No voltage open-contact (Max. AC250V/1A, DC30V/2A) |
Input/Output / Operation stop output | No voltage open-contact (Max. AC250V/1A, DC30V/2A) |
Input/Output / Pump output | No voltage open-contact (Max. AC250V/1A, DC30V/2A) |
Input/Output / Emergency stop input | No-voltage input |
Input/Output / Operation stop input | No-voltage input |
Input/Output / Error reset input | No-voltage input |
Input/Output / External temperature sensor *8 | Pt100 |
Input/Output / Ethernet | 10BASE-T/100BASE-TX Socket(TCP/IP)、MC protocol(UDP/IP)、Modbus TCP |
Display / operation method | Monochrome display, key input |
Log data | Recorded items: Date and time, error number, circulation water set temperature, circulation water outlet temperature, external temperature, chiller run/stop, pump/fan/compressor run/stop, pump independent run status, emergency stop command input terminal status, run-stop command input terminal status, error reset command input terminal status, false warning output status, compressor high-pressure pressure, compressor low-pressure pressure, compressor ejection temperature, compressor intake temperature, water empty sensor status, fan control status, coolant operation volume, high-pressure protection control status, low-pressure protection control status, overheating protection control status, freezing protection control status. Recording period: Approx. 1 year and 6 months Recording interval *9: 2 minute intervals Export method: USB memory, Socket communication |
Functions | Graph display, chiller operation status display, error history display, operation time display, calendar, write memo, water temperature error settings, operation timer settings, password settings, key lock, freeze protection operation, log data USB memory write, external temperature sensor input, cascade control |
*1. Values at operating use area temperature 25℃, circulating water temperature 20℃, and circulating water rated flow rate.
*2. When using clean water, use water that meets the Japan Refrigeration and Air Conditioning Industry Association water quality standards (JRA-GL 02:1994). Use water with an electrical conductivity of 1μS/cm or higher (above indicates poor purity. Example: 100μS/cm). Using circulating water outside the specifications may result in reduced chiller performance and early failure. When using below 10°C, use antifreeze (aqueous ethylene glycol solution of appropriate concentration).
*3. Based on chiller temperature gauge display values under constant load, surrounding temperature of 25℃, circulation water temperature of 20℃, and circulation water flow at rated volume.
*4. Value calculated based on circulation water flow of 4ℓ/min. To prevent pump breakdown, avoid running the chiller with circulation water flow below 4ℓ/min.
*5. Excluding the protruded part.
*6. Maintain power supply voltage within ±10% of rated voltage.
*7. Values measured with a 1m face, 1m height, and no load stability.
*8. External temperature sensor not included. The user prepares the external temperature sensor.
*9. Errors are recorded in 5 second intervals from approximately 1 minute before.
■Piping port sizes
Circulating water inlet port : Rc 3/4, [Tightening torque (recommended)] 50 N·m
Circulating water outlet port : Rc 3/4, [Tightening torque (recommended)] 50 N·m
* Lift: 1 [m] = 0.0098 [MPa]