1. HOME
  2. Product information
  3. Thermal control equipment Control Panel Cooling unit ENC Series
  4. Control panel cooling unit Product lineup
  5. ENC-G2240L

Control panel cooling unit ENC-G2240L

Control Panel Cooling unit
Freon-gas Special specifications
Side-mounting

ENC-G2240L

ENC Series

Control Panel Cooling unit Freon-gas Special specifications ENC-G2240L

Compatible with a 400 V power supply, making it ideal for various plants and overseas facilities.

  • Freon-gas
  • Special specifications
Cooling capacity(W) 2000/2200
Rated Voltage(V) Three-phase 380 to 415V AC/400 to 460V AC
Mounting type Side-mounting
External dimensions(mm) H1200×W450×D260
Weight(kg) 62

Product Details for ENC-G2240L

Specifications

(50/60Hz)

Mounting type Side-mounting
Cooling capacity(W) 2000/2200
Setting temperature range(℃) 25 to 45
Ambient Temperature(℃) 20 to 55
Ambient Humidity(%RH) 10~85 (No condensation)
Dimensions(mm) H1200×W450×D260
Weight(kg) 62
Coating Color Munsell 5Y 7/1 Equivalent color of light beige
Rated voltage(V) Three-phase 380 to 415V AC/400 to 460V AC
Current consumption : Rating(A) 1.7/1.9
Current consumption : Max(A) 2.2/2.5
Starting Current(A) 12/13
Power consumption : Rating(W) 1000/1200
Power consumption : Max(W) 1350/1700
Noise Resistance LEVEL4 by Fast Transient / Burst Immunity Test
Vibration resistance Equivalent to JIS Z 0200 Level1
Dustproof and splashproof protection grade Equivalent to IP54 (internal circulation route)
Certification
Refrigerant / Amount(g) R134a 300g
Noise (dB (A)) Approx. 65/67
External output Alarm output (No-voltage/normal open: resistive load 250V 2A)
Display Internal temperature/Error display LED/RUN LED

Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal temperature is 35°C - 40%. (measurement conditions: JIS-C-9612 air enthalpy method))
MAX value: Value at the maximum ambient temperature allowed and an operating ambient humidity of 40%RH.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.

External dimensions

ENC-G2240L External dimensions

Diagram of Panel Cutout

ENC-G2240L Diagram of Panel Cutout

Capacity characteristic chart

ENC-G2240L Capacity characteristic chart

*Contact our sales representative if you are using the control panel cooler in an environment close to the permissible ambient temperature upper limit.

[Caution]
To ensure proper operation of this equipment, read the operation manual before use.
Depending on model and quantity, separate charter delivery may be arranged (additional costs apply). 
Overseas at the time of delivery, we recommend packing for overseas separately.
Please check through the cooler between the FA and the power (circuit breakers) to the appropriate specification of the FA breaker cooler.
Cause of failure and be used at the rated power supply out of range.
Please use the service and maintenance on a regular basis.
Failure to maintain regular maintenance, you may be a factor in product performance degradation trouble.
When the outside temperature is low in winter, please do not let the FA cooler continuous operation.
When disposing of this product, you should comply with various laws and regulations, please go to the appropriate.