Control panel cooling unit ENC-GR300EX

Control Panel Cooling unit
Non-freon-gas Compact
Top-mounting

ENC-GR300EX

ENC Series

Control Panel Cooling unit Non-freon-gas Compact ENC-GR300EX
  • Non-freon-gas
  • Compact
Cooling capacity(W) 290/300
Rated Voltage(V) Single-phase 200V AC
Mounting type Top-mounting
External dimensions(mm) H232×W450×D250
Weight(kg) Approx. 15

Product Details for ENC-GR300EX

Specifications

(50/60Hz)

Mounting type Top-mounting
Cooling capacity(W) *1 290/300
Setting temperature range(℃) 25 to 45
Ambient Temperature(℃) *2 20 to 50
Ambient Humidity(%RH) *2 10 to 85 (No condensation)
Dimensions(mm) H232×W450×D250
Weight(kg) Approx. 15
Coating Color Munsell 5Y7/1 (light beige equivalent)
Rated voltage(V) Single-phase 200V AC
Current consumption *3 : Rating(A) *4 1.3/1.1
Current consumption *3 : Max(A) *5 1.5/1.3
Starting Current(A) 2.9/2.7
Power consumption *3 : Rating(W) *4 220/220
Power consumption *3 : Max(W) *5 265/270
Recommended breaker capacity (A) 5
Vibration resistance JIS Z0200 Level 1 equivalent
Dustproof and splashproof protection grade *6 IP54 equivalent (internal circulation path)
Refrigerant / Amount(g) R1234yf 105g
Noise (dB (A)) Approx. 60/65
External output Alarm output (no voltage, normally open: 250 V and 2 A resistive load); Setting can be switched to no voltage, normally closed
Display Panel internal temperature / Error code / RUN

*1 The rated cooling capacity at 35°C ambient temperature, 40% relative humidity, and 200 V power-supply voltage (100 V for 100 V models only).
(Test method: JIS B 8615-1 indoor air enthalpy test method)
*2 The range of ambient temperature and ambient humidity defines the operating range and is not a guarantee of the rated performance.
*3 The values for the current consumption and power consumption are based on cooling operation.
*4 The rated value at 35°C ambient temperature, 40% relative humidity, and 200 V power-supply voltage (100 V for 100 V models only).
*5 The ambient temperature at the maximum value is subject to specific limitations.
*6 When the drain pipe section is sealed.

External dimensions

ENC-GR300EX External dimensions

Diagram of Panel Cutout

ENC-GR300EX Diagram of Panel Cutout

Capacity characteristic chart

ENC-GR300EX Capacity characteristic chart

*Contact our sales representative if you are using the control panel cooler in an environment close to the permissible ambient temperature upper limit.

[Caution]
To ensure proper operation of this equipment, read the operation manual before use.
Depending on model and quantity, separate charter delivery may be arranged (additional costs apply).
Overseas at the time of delivery, we recommend packing for overseas separately.
Please check through the cooler between the FA and the power (circuit breakers) to the appropriate specification of the FA breaker cooler.
Cause of failure and be used at the rated power supply out of range.
Please use the service and maintenance on a regular basis.
Failure to maintain regular maintenance, you may be a factor in product performance degradation trouble.
When the outside temperature is low in winter, please do not let the FA cooler continuous operation.
When disposing of this product, you should comply with various laws and regulations, please go to the appropriate.