290/300
External dimensions(mm)
H232×W450×D250
ENC Series
Cooling capacity(W) | 290/300 |
---|---|
Rated Voltage(V) | Single-phase 200V AC |
Mounting type | Top-mounting |
External dimensions(mm) | H232×W450×D250 |
Weight(kg) | Approx. 15 |
(50/60Hz)
Mounting type | Top-mounting |
---|---|
Cooling capacity(W) *1 | 290/300 |
Setting temperature range(℃) | 25 to 45 |
Ambient Temperature(℃) *2 | 20 to 50 |
Ambient Humidity(%RH) *2 | 10 to 85 (No condensation) |
Dimensions(mm) | H232×W450×D250 |
Weight(kg) | Approx. 15 |
Coating Color | Munsell 5Y7/1 (light beige equivalent) |
Rated voltage(V) | Single-phase 200V AC |
Current consumption *3 : Rating(A) *4 | 1.3/1.1 |
Current consumption *3 : Max(A) *5 | 1.5/1.3 |
Starting Current(A) | 2.9/2.7 |
Power consumption *3 : Rating(W) *4 | 220/220 |
Power consumption *3 : Max(W) *5 | 265/270 |
Recommended breaker capacity (A) | 5 |
Vibration resistance | JIS Z0200 Level 1 equivalent |
Dustproof and splashproof protection grade *6 | IP54 equivalent (internal circulation path) |
Refrigerant / Amount(g) | R1234yf 105g |
Noise (dB (A)) | Approx. 60/65 |
External output | Alarm output (no voltage, normally open: 250 V and 2 A resistive load); Setting can be switched to no voltage, normally closed |
Display | Panel internal temperature / Error code / RUN |
*1 The rated cooling capacity at 35°C ambient temperature, 40% relative humidity, and 200 V power-supply voltage (100 V for 100 V models only).
(Test method: JIS B 8615-1 indoor air enthalpy test method)
*2 The range of ambient temperature and ambient humidity defines the operating range and is not a guarantee of the rated performance.
*3 The values for the current consumption and power consumption are based on cooling operation.
*4 The rated value at 35°C ambient temperature, 40% relative humidity, and 200 V power-supply voltage (100 V for 100 V models only).
*5 The ambient temperature at the maximum value is subject to specific limitations.
*6 When the drain pipe section is sealed.
*Contact our sales representative if you are using the control panel cooler in an environment close to the permissible ambient temperature upper limit.
[Caution]
To ensure proper operation of this equipment, read the operation manual before use.
Depending on model and quantity, separate charter delivery may be arranged (additional costs apply).
Overseas at the time of delivery, we recommend packing for overseas separately.
Please check through the cooler between the FA and the power (circuit breakers) to the appropriate specification of the FA breaker cooler.
Cause of failure and be used at the rated power supply out of range.
Please use the service and maintenance on a regular basis.
Failure to maintain regular maintenance, you may be a factor in product performance degradation trouble.
When the outside temperature is low in winter, please do not let the FA cooler continuous operation.
When disposing of this product, you should comply with various laws and regulations, please go to the appropriate.