Chiller PCU-F3000

Chiller
Pumpless and tankless chillers

PCU-F3000

PCU Series

Chiller Pumpless and tankless chillers PCU-F3000
Cooling capacity (W) 2800/3200
Temperature stability (℃) ±0.1
Circulated water flow rate range (ℓ/min) 10 to 60
Circulating water fixed flow rate (ℓ/min) 15/15

Product Details for PCU-F3000

Specifications

(50 / 60Hz)

Cooling scheme Air-cooling type
Cooling capacity (W) *1 2800 / 3200
Circulated water *2 Clean water, Ethylene glycol solution (concentration 15 wt% or less), Propylene glycol solution (concentration 15 wt% or less)
Temperature stability (℃) *3 ±0.1
Use Area Temperature (℃) 5 to 45
Temperature control / Fixed system Control target *4 : Outlet liquid temperature or External temperature sensor measurement value
Range[℃] : 5 to 40
Temperature control / Synchronized system Reference *4 : External temperature sensor measurement value
Control target : Outlet liquid temperature
Synchronization range [℃] : -10.0 to +10.0 relative to the reference temperature (factory default setting: 0.0)
Circulated water flow rate range (L/min) 10 to 60
Circulating water fixed flow rate (ℓ/min) 15/15
Circulating water maximum operating pressure (MPa) 1
Dimensions (mm) *5 H697×W400×D600
Coating Color Munsell N-87
Weight (kg) Approx. 51
Casters (Φmm×unit) 50×4
Rated Voltage (V) *6 3-phase 200 VAC
Power Consumption (kW) *1 0.7 / 1.0
Current consumption (A) *1 2.7 / 3.3
Recommended breaker capacity (A) 10
Circulating water inlet / outlet port size Rc3/4
Drain discharge port size G1/2
Components / Compressor Fully sealed rotary type
Components / Condenser Parallel flow condenser
Components / Evaporator Structure : Plate-type heat exchanger
Material : SUS316 (copper brazing)
Refrigerator R1234yf 340g
Noise (dB) *7 51 / 54
Safety circuit / Compressor Thermal protector, electromagnetic switch
Safety circuit / Fan motor Thermal protector, current fuse
Input / Alarm output No voltage, normally open (maximum 250V AC and 1 A/30 V DC and 2A)
Input/Output / Water temperature upper / lower limit output No voltage, normally open (maximum 250V AC and 1 A/30 V DC and 2A)
Input/Output / Operation stop output No voltage, normally open (maximum 250V AC and 1 A/30 V DC and 2A)
Input/Output / Emergency stop input No-voltage input
Input/Output / Operation stop input No-voltage input
Input/Output / Error reset input No-voltage input
Input/Output / External temperature sensor *7 Pt100
Input/Output / Ethernet Communication standard : 10BASE-T/100BASE-TX
Communication protocol : Socket(TCP/IP)、MC protocol(UDP/IP)、Modbus TCP
Log data Recorded items:
Date and time, error number, circulating water set temperature, circulating water outlet temperature, external temperature, chiller run/stop, fan/compressor run/stop, emergency stop command input terminal status, run-stop command input terminal status, error reset command input terminal status, pseudo-alarm output status, compressor high pressure, compressor low pressure, compressor discharge temperature, compressor intake temperature, fan control status, cooling operation amount, high-pressure protection control status, low-pressure protection control status, overheating protection control status, freezing protection control status.
Recording period: Approx. 1 year and 6 months
Recording interval : 2 minute intervals
Export method: USB memory, Socket communication
Functions Graph display, operation status display, error history display, operation time display, calendar, memo, water temperature error setting, operation timer setting, password setting, key lock, exporting log data via USB flash drive, external temperature sensor input, cascade control, external synchronized control

*1 Values when ambient temperature is 25℃, circulating water temperature is 20℃, circulating water is at rated flow rate, and circulating water is clean water.
*2 When using clean water, be sure to use water that meets the water quality standards of the Japan Refrigeration and Air Conditioning Industry Association (JRA-GL 02:1994). The electrical conductivity should be at least 1μS/cm (higher conductivity indicates lower purity; Example: 100μS/cm). Use of circulating water that does not meet the specifications may result in poor chiller performance and premature failure.
*3 Based on chiller temperature gauge readings when load is constant, ambient temperature is 25℃, circulating water temperature is 20℃, and circulating water is at rated flow rate.
*4 An external temperature sensor (Pt100) is not included. Please prepare one yourself.
*5 Excluding protrusions.
*6 Use a power supply voltage within ±10% of the rated voltage.
*7 Values measured at 1m from the front of the device and at a height that comes to the center of the device, and at no load stability.
*8 When an error occurs, recorded at 5-second intervals from approximately 1minute before the error occurrence.

External dimensions

PCU-F3000 External dimensions

■Piping port sizes
Circulating water inlet port : Rc 3/4, [Tightening torque (recommended)] 50 N·m
Circulating water outlet port : Rc 3/4, [Tightening torque (recommended)] 50 N·m

Cooling capacity characteristic charts

PCU-F3000 Cooling capacity characteristic charts

[Ambient temperature] a: 5℃, b: 25℃, c: 32℃, d: 40℃, e: 45℃

Pressure loss characteristic charts