  5. PAU-GR800SE-HC

Precision air conditioners (TCU/ECU) PAU-GR800SE-HC

Precision air conditioners (TCU/ECU)
Temperature and humidity control

PAU-GR800SE-HC

PAU Series

Precision air conditioners (TCU/ECU) Temperature and humidity control PAU-GR800SE-HC

Revolutionary compact design and non-freon refrigerant.

  • Air-cooling type
  • Temperature and humidity control
Air outlet volume(m3/min) 3.0(Normal mode)
Cooling capacity(W) 850 (970)
Thermal capacity(W) 630
Rated voltage(V) Single-phase, 200 to 240 VAC
Control models Temperature and humidity control
External Dimensions(mm) H1050×W400×D665
Weight(kg) 85

Product Details for PAU-GR800SE-HC

Specifications

Cooling scheme Air-cooling type
Control models Temperature and humidity control
Cooling capacity(W) *1 850 (970)
Thermal capacity(W) *2 630
Humidity capacity(g/㎏(DA)) *3 4.01
Dehumidifying capacity(g/㎏(DA)) *4 7.02
Temperature control precision(℃) *5 ±0.1
Temperature control range(℃) *6 20 to 30
Humidity control precision(%RH) *5 ±1.0
Humidity control range(%RH) *6 35 to 75
Ambient temperature(℃) 20 to 35 (Temperature change gradient: Within 1℃/1h)
Ambient humidity(%RH) 15 to 85 (Humidity change gradient: within 5%RH/1h) (No condensation)
Air outlet volume(m3/min) *8 3.0 (Normal mode / Energy saving mode)
1.8 (Dry mode)
External Dimensions(mm) *9 H1050×W400×D665
Weight(kg) 85
Coating Color Munsell N-87 Equivalent color of gray
Blower duct connection diameter(mm) φ75
Rated voltage(V) *10 Single-phase, 200 to 240 VAC
Current consumption(A) ※11 3.7(Rated) / 4.7(MAX)
Power consumption(W) *11 590(Rated) / 755(MAX)
Humidifier / Water supply pressure(MPa) 0.2 to 1.0
Humidifier / Water supply connection port 15A Socket
Drain connection diameter 20A Socket
Frame drain connection port diameter 15A Socket
Refrigerant(g) R1234yf 300g
Exhaust air volume(m3/min) *12 6.0
Noise (dB (A)) *13 65
Output/Main unit abnormal output Normal open / no-voltage (250 VAC/2A / resistive load)

*1 Cooling capacity is based on a 25 ℃/50% RH use area temperature and humidity at a distance of 4 meters in front of the duct.
( ) internal cooling capacity is based on 30 ℃/70% RH use area temperature and relative humidity at a distanc e of 4 meters in front of the duct .
*2 Thermal capacity is based on 25℃/50% RH use area temperature and relative humidity when a distance of 4 meters in front of the duct.
*3 Humidification capacity is based on 25℃/50% RH use area temperature and relative humidity when a distance of 4 meters in front of the duct when the SV value is set to 25℃ at a duct 4 m ahead.
*4 Dehumidifying capacity is based on 30℃/70% RH use area temperature and relative humidity when operating in dry mode at a distance of 4 meters in front of the duct.
*5 The temperature and humidity control accuracy is based on the method prescribed in JTMK01 Constant Temperature Humidistat Bath - Performance Testing Method and Performance Display Method (Japan T esting Machine Association). Only the value indicated by the te mperature controller built into the air conditioner at the main unit blow off port is guaranteed to be accurate and thermal inter ference due to the duct etc. is not covered by the precision gu arantee. In addition, the purpose of this product is to suppress temperature fluctuations in the air and so the absolute value of the temperature is not guaranteed. (A bias fu nction for compensation is built into the system.)
*6 The temperature and humidity may not be controllable even if they are within the set range depending on the ambient temperature.
*7 Dimensions excluding operation panel protrusions, blowout flanges, casters and their mounting parts.
*8 The consumption current and power consumption indicated these fluctuate depending on the temperature and humidity of the ambient environment and the operating conditions.
*9 Waste heat is discharged from the device because it is air -cooled. (with optional exhaust chamber)
・For the actual installation, check the specifications and precau tions stated in the instruction manual.
・Maintain power supply voltage within ±10% of rated voltage.

External dimensions

PAU-GR800SE-HC External dimensions

Temperature / humidity sensor

PAU-GR800SE-HC Temperature / humidity sensor

[Caution]
To ensure proper operation of this equipment, read the operation manual before use.
Depending on model and quantity, separate charter delivery may be arranged (additional costs apply).
Overseas at the time of delivery, we recommend packing for overseas separately.
After verifying the specifications, insert an appropriate breaker (circuit breaker for wiring) between the product and power supply.
Cause of failure and be used at the rated power supply out of range.
Please use the service and maintenance on a regular basis.
Failure to maintain regular maintenance, you may be a factor in product performance degradation trouble.
When disposing of this product, you should comply with various laws and regulations, please go to the appropriate.