1. HOME
  2. Product information
  3. Heat-control equipment control panel cooling unit ENC Series
  4. 制御盤用クーラーの選び方

Control panel cooling unit

かんたん機種選定ガイド

Selection method

List of heat output by device

Control panel cooling unit

1. How to select panel cooler [indoor installation]

cooling capacity required to maintain the desired temperature inside panel can be calculated using the formula below.

①Total heat generation inside panel

The total heat generated by the devices housed inside the panel.
*For the heat output of each device, please refer to the heat output list by device.

② Heat transfer rate

The rate at which heat penetrates from outside the panel into the panel.
This varies depending on the type of sheet metal and thickness, but for a 2mm thick steel plate it is approximately 5 [W/m2・℃].

③ Maximum ambient temperature

The highest temperature expected in environment in which the unit will be installed.

④ Desired temperature inside the panel

Desired internal temperature (recommended temperature is 35°C).

⑤ panel effective surface area

Total surface area of all surfaces in contact with the atmosphere of the target panel (for freestanding panels, surface area excluding the bottom).

2. How to select panel cooler [outdoor installation]

For outdoor installation, add the amount of energy from sunlight to the selection result of panel cooler for indoor installation calculated in 1. panel cooler selection method [indoor installation].

Required cooling capacity [W]
= Total solar intrusion heat + Necessary when using an indoor panel cooling capacity (1. panel cooler Refer to the item [Indoor installation] of the selection method)

How to calculate total solar radiation and heat penetration

1) Calculate the amount of heat entering through solar radiation.

The amount of sunlight varies depending on the installation location, date, time and orientation.

*Sample data of solar radiation on each surface (Tokyo area, July 22nd, clear skies) Unit: W/m²

  Top north face East side south side West side
11 o'clock 1026.7 302.8 302.8 305.1 77.3
12 o'clock 1064.0 78.3 78.3 325.9 78.3
13:00 1043.0 78.8 78.8 310.1 307.7
14:00 980.2 79.1 79.1 261.7 523.3
3pm 872.1 80.7 80.7 179.8 715.3

Therefore, the required amount of solar heat radiation is calculated for each surface and the sum of the calculations is the amount of solar heat radiation required. The solar heat radiation for each surface can be calculated using the following formula.

Total solar radiation heat intrusion = Temperature rise on the surface of the housing on each side (equivalent to the rise in outside temperature) x Overall heat transfer coefficient x Surface area of each side
Equivalent outside temperature rise [℃] =
Solar radiation on each surface [W/m²] ×
Solar absorptivity Heat transfer coefficient on outer surface of enclosure [W/m²・℃]
Terminology
  • Heat transfer coefficient (W/m² °C): Ratio of the amount of heat that enters (or dissipates) by heat conduction to the area when there is a temperature difference between the ambient temperature (the temperature at which the enclosure surface rises) and the desired temperature. panel varies depending on the board thickness and material, but is defined as 5 to 6 W/m² °C by the Panel Heat Related Equipment Manufacturers Association.
  • "Heat transfer coefficient on the outside of the housing (W/m²・℃)" - It is estimated to be approximately 10W/m²・℃ when there is no wind, and approximately 15W/m²・℃ when the wind speed is 1 to 2 m/s. The higher the wind speed, the greater the heat transfer coefficient.
  • "Casing surface temperature rise (equivalent to outside air temperature rise)": This refers to the equivalent temperature rise due to solar radiation.

From the above, we can see that the temperature will vary depending on the area where the panel is installed, the color and condition of the panel surface, the condition of the panel's outer walls (thickness, double structure, installation of sunshades, etc.), and the condition of the wind circulating outside the panel.

As an example, let's calculate using panel with the following conditions.

◎ Height 2000mm, width 1000mm, depth 500mm◎ Door facing south◎ Tokyo area, July 22nd, clear skies, 2pm, no wind◎ Panel thickness 2mm, paint color: light beige, wall surface is single-layer structure

Face position solar radiation
(W/m²)
solar absorptance Outer surface of the housing
heat transfer coefficient
(W/m²・℃)
Fairly open air
Temperature rise
(℃)
heat transfer rate
(W/m²・℃)
Area of surface (m²) Solar heat (W)
Top 980.2 0.5 10 49.01 5 0.5 122.5
north face 79.1 0.5 10 3.955 5 2 39.6
East side 79.1 0.5 10 3.955 5 1 19.8
south side 261.7 0.5 10 13.085 5 2 130.9
West side 523.3 0.5 10 26.165 5 1 130.8
Total solar radiation and heat infiltration 443.6

Caution! As the surface of the disc becomes dull over time, the absorption rate changes, so it is necessary to select a product with safety factor in mind.

3) Select the required cooling capacity by applying it to capacity characteristics graph of each panel cooler.

<<Notes on selection>>

  1. Please note that the amount of heat generated by inverters, servo amplifiers, etc. varies greatly depending on how they are used, motor torque, etc.
  2. For inverters with a rating output of 50 kW or more, the amount of heat generated varies greatly depending on the manufacturer, so please check with the manufacturer.
  3. When selecting a model, please select one that exceeds the required rating capacity and cooling capacity.
  4. Please note that capacity calculated using the above formula are only a guideline and are not absolute values.
  5. Please note that depending on the sealing of the panel, the position with the heating element, and the convection in the chamber, the expected cooling capacity may not be obtained.
  6. Dirty filter and deterioration of the fan motor may lead to a decrease in cooling capacity, so please perform regular maintenance.

List of heat output by device

1. power supply and transformer equipment

Equipment stored inside the panel Heat generation (reference value) remarks
Small transformer rating capacity
~100VA Approximately 15%
~300VA About 10%
~1kVA Approximately 7%
~3kVA About 5%
~5kVA Approximately 4%
  • The smaller the size, the greater the heat generation rate.
Large transformer
(single-phase)
rating capacity
Up to 20kVA About 2%
Up to 100kVA Approximately 1.5%
Up to 300kVA About 1%
 
Large transformer
(three phase)
rating capacity
Up to 20kVA Approximately 2.2%
Up to 100kVA About 2%
Up to 200kVA Approximately 1.5%
Up to 300kVA Approximately 1.4%
Up to 500kVA Approximately 1.2%
 
Voltage regulator Approximately 10% of the rating capacity  
large resistor About 1/3 of rating capacity  
constant voltage power supply rating capacity
~2kVA Approximately 15%
Up to 10kVA About 10%
 
uninterruptible power supply supply
(UPS)
Output Capacity
~1kVA Approximately 20%
~5kVA Approximately 20%
Up to 10kVA Approximately 20%
Up to 20kVA Approximately 15%
~50kVA Approximately 15%
Up to 100kVA Approximately 15%
  • The smaller the size, the greater the heat generation rate.
  • The heat generation amount is the value when the battery is in a floating charge state.
  • Continuous inverter power supply system
DC stabilized power supply
(switching regulator)
Approximately 20 to 30% of the rating capacity
  • The smaller the size, the greater the heat generation rate.
  • This is the amount of heat generated when rating capacity is 100%.
Low-Voltage Capacitor Approximately 0.2 to 0.3% of rating capacity
  • rating capacity is kVA.
    reference
    (1kVA = 265.3μF)

2. Amplifiers

Equipment stored inside the panel Heat generation (reference value) remarks
AC servo amplifier rating capacity
~0.1kW About 50%
~0.5kW Approximately 15%
~1kW Approximately 8%
~3kW About 5%
~5kW Approximately 4%
~11kW Approximately 3.5%
~22kW Approximately 3%
  • The smaller the size, the greater the heat generation rate.
  • This is the amount of heat generated when rating capacity is 100%.
  • The numbers are general guidelines.
    For details, please contact each manufacturer.
inverter rating Output
~0.4kW Approximately 12.5%
~0.75kW Approximately 11%
~1.5kW Approximately 8%
~2.2kW Approximately 7%
~3.7kW Approximately 6%
~7.5kW Approximately 6%
~11kW About 5%
~22kW Approximately 4.5%
~75kW Approximately 4%
~280kW Approximately 3%
  • The smaller the size, the greater the heat generation rate.
  • This is the amount of heat generated when rating capacity is 100%.
  • The numbers are general guidelines.
    For details, please contact each manufacturer.
AC reactor
(200V system)
rating capacity
3.7kW About 10W
5.5kW About 17W
7.5kW Approximately 19W
11kW About 20W
15kW Approximately 29W
22kW Approximately 33W
30kW About 39W
37kW About 41W
45kW Approximately 47W
55kW About 55W
75kW About 65W
90kW About 76W
110kW Approximately 83W
  • Heat output indication.
  • Heat generation when input voltage is 50Hz, voltage balance is 0%, and motor load is 100%.
AC reactor
(400V system)
rating capacity
3.7kW About 8W
5.5kW About 11W
7.5kW About 13W
11kW About 14W
15kW Approximately 19W
18.5kW About 27W
22kW About 36W
30kW About 39W
37kW About 50W
45kW About 56W
55kW Approximately 66W
75kW About 71W
90kW Approximately 86W
110kW About 94W
132kW About 119W
160kW About 135W
200kW About 155W
220kW About 170W
280kW About 210W
  • Heat output indication.
  • Heat generation when input voltage is 50Hz, voltage balance is 0%, and motor load is 100%.
DC reactor
(200/400V system)
rating capacity
0.4kW About 2W
0.75kW About 3W
1.5kW About 6W
2.2kW About 8W
3.7kW About 14W
5.5kW Approximately 19W
7.5kW About 25W
11kW Approximately 31W
15kW About 36W
18.5kW About 40W
22kW About 52W
30kW Approximately 60W
37kW Approximately 67W
45kW About 95W
55kW Approximately 100W
  • Heat output indication.
Braking resistor and control unit
(200/400V system)
rating capacity
3.7kW Approximately 190W
5.5kW Approximately 280W
7.5kW About 380W
11kW Approximately 550W
15kW About 750W
18.5kW About 930W
22kW About 1100W
30kW About 1500W
37kW Approximately 1900W
45kW Approximately 2300W
55kW Approximately 2800W
75kW Approximately 3800W
90kW Approximately 4500W
110kW Approximately 5500W
  • Heat output indication.
  • This is the heat generation amount when the control torque is 100% and the braking frequency is 5%.
Thyristor
(single-phase)
rating current
~25A About 50W
~35A About 55W
~50A About 75W
~75A Approximately 90W
~100A About 120W
~150A About 200W
~250A About 350W
~350A Approximately 400W
~450A About 560W
~600A About 700W
  • Heat output indication.
Thyristor
(three phase)
rating current
~25A Approximately 90W
~35A About 115W
~50A About 175W
~75A About 250W
~100A About 320W
~150A Approximately 520W
~250A About 930W
~350A About 1150W
~450A Approximately 1600W
~600A Approximately 2000W
  • Heat output indication.

3. Wiring equipment

Equipment stored inside the panel Heat generation (reference value) remarks
Circuit breaker
(MCCB)
rating capacity
~20A About 7W
~50A About 14W
~100A Approximately 21W
~225A About 45W
Up to 400A About 115W
  • Heat generation at 100% rating current.
  • In the case of 3P (proportional to polarity)
Earth leakage circuit breaker (ELCB) rating capacity
~225A MCCB+ 5W approx.
~400A MCCB+30W (earth leakage electronic circuit, etc.)
  • Heat generation at 100% rating current.
  • In the case of 3P (proportional to polarity)
    However, the leakage current electronic circuitry is not affected by polarity.
electromagnetic contactor rating capacity
~4kW About 7W
~11kW About 15W
~22kW About 30W
~37kW About 50W
~55kW Approximately 90W
~110kW About 200W
~160kW About 340W
~200kW About 460W
  • Heat generation at 100% rating current.
Thermal overload relay
(thermal)
rating current
~15A 2W/extreme
~30A 3W/Extreme
~100A 7W/Extreme
~150A 9W/Extreme
~450A 10W/extreme
~600A 12W/Extreme
  • The amount of heat generated when the maximum set current value is applied.
electromagnetic relay Approximately 5W per unit
  • Heat generation at 100% rating current.

4. Control equipment

Equipment stored inside the panel Heat generation (reference value) remarks
Small relay
Mini Relay 1~2W/piece
Power Relay 2~3W/piece
 
Solid State Relay
(SSR)
Load current value x 1.8W  
temperature controller current consumption is considered to be the amount of heat generated.  
PLC small PLC
AC power supply type
I/O points: 10 to 40 points 30 to 50W
I/O points: 64 or more Number of I/O points x 1W
DC power supply type Number of I/O points x 0.5W

power consumption of a standard PLC power supply unit

 
PC power consumption of power supply unit  
LCD monitor Approximately 20W per unit  
Touch-panel Approximately 100W per unit  

5.Other

Equipment stored inside the panel Heat generation (reference value) remarks
fan motor
90□ size About 10W
120□ size About 20W
140□ size About 40W
150φ size About 55W
180□ size About 55W
  • Rating input is considered the heat output.
  • For axial fan motor.
  • For AC input.
  • The size is the frame size.

Note! The above heat output data for each device is based on data published by the Panel Heat-Related Equipment Industry Association, with additional data that we have independently researched.
The heat output of each device is a guideline, so if you would like to know the exact heat output, please contact the device manufacturer.

Inquiry

For product inquiries, quote requests, etc.
Please feel free to contact us.

TEL: 0120-945-354

This service is not available from some IP phones.

support@apiste.co.jp