Cooling capacity (W) | 14200 |
---|---|
Heating capacity (W) | 2500 |
Water setting temperature range (℃) | -5 to 45 |
Temperature stability (℃) | ±0.1 |
Circulated water flow rate range (ℓ/min) | 20~70 |
Product Details for PCU-SL15000W
Specifications
(50 / 60Hz)
Cooling scheme | Water-cooling type |
---|---|
Cooling capacity (W) | 14200 |
Heating capacity (W) | 2500 |
Circulated water | Pure water (over 1μs/cm), distilled water, ethylene glycol (less than 30% density), top water |
Water setting temperature range (℃) | -5 to 45 |
Temperature stability (℃) | ±0.1 |
Use Area Temperature (℃) | 2~45 |
Circulated water temperature range (Clear water) (℃) | 5~45 |
Circulated water temperature range (Anti-freeze water) (℃) | -5~45 |
Circulated water flow rate range (L/min) | 20~70 |
Circulated water pressure range (Mpa) | 0.7 or less |
Circulating pump/Head (m) | 51m (45L/min / 3600rpm) (max. lift 71m) |
Maximum tank capacity (ℓ) | 35 |
Cooling water / Temperature range (℃) | 5~45 |
Dimensions (mm) | H1349×W850×D750 |
Coating Color | DIC G-260 (Munsell : N7.5 or suitable color) |
Weight (kg) | 139 |
Rated Voltage (V) | 3-phase AC200~230V |
Power Consumption (kW) | 4.6 |
Current Consumption/MIN (A) | 14.0 |
Current Consumption /MAX (A) | 19.0 |
Voltage source capacity (kVA) | 7.6 |
Recommended breaker capacity (A) | 30 |
Components / Compressor | Shutting tightly Roundabout system |
Components / Condenser | Plate-type heat exchanger |
Components / Refrigerator | Plate-type heat exchanger |
Components / Evaporator | 70 |
Components / Circulating pump | Multistep spiral dipping mandrel |
Certification | CE |
Refrigerator | R410A 1250g |
Noise (dB) | 58 |
Safety circuit / Compressor | Motor protector |
Safety circuit / Refrigeration cycle | Pressure switch |
Safety circuit / Circulating water circuit | Water pressure sensor, float switches for water shortage |
Input/Output / Alarm output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Water temperature upper / lower limit output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Operation stop output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Pump output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Emergency stop input | No-voltage input |
Input/Output / Operation stop input | No-voltage input |
Input/Output / Error reset input | No-voltage input |
Input/Output / Ethernet | Communication standard: Ethernet 10BASE-T / 100BASE-TX Communication protocol: Socket (TCP / IP), MC protocol (UDP / IP) IP address: IPv4 |
Safety measures | CE (Low-voltage command, EMC command) |
*Cooling capacity, power consumption, current consumption rating: 20 ºC circulating water temperature, 45L/min circulation water flow rate, 32ºC ambient temperature and cooling water rated flow rate (cooling water volume requires rated performance).
*Heating capacity: During start-up operation at an ambient temperature of 40 °C. Varies depending on the ambient temperature.
*Circulated water: Use water with a purity of 1 μS/cm or more (low purity). Pure water: Water quality standards of The Japan Refrigeration and Air Conditioning Industry Association (JRA GL-02-1944)
* Required cooling water flow rate: The amount of cooling water required for the rated capacity.
* Temperature stability: Depends on the display value of the main body temperature indicator at a constant load.
*MAX current consumption: When the circulating water temperature is 20 °C, the circulating water flow rate is 70 L/min, and circulating water temperature is 45 °C.
*Vibration resistance: Up to 100 Hz under the test conditions of the MIL-STD-810F standard.
*Operating noise: Measured at a horizontal distance of 1 m and height of 1 m.
External dimensions
■Piping port sizes
Circulating water outlet port : Rc 1, [Tightening torque (recommended)] 80 N·m
Circulating water inlet port : Rc 1, [Tightening torque (recommended)] 80 N·m
Cooling water inlet port : Rc 3/4, [Tightening torque (recommended)] 50 N·m
Cooling water outlet port : Rc 3/4, [Tightening torque (recommended)] 50 N·m
Air vent : Rc 3/8, [Tightening torque (recommended)] 25 N·m
Cooling water drain port : Rc 3/8, [Tightening torque (recommended)] 25 N·m
Tank drain port : Rc 3/8, [Tightening torque (recommended)] 25 N·m
Overflow drain port : Rc 1, [Tightening torque (recommended)] 80 N·m
Automatic water supply port (optional) : Rc 3/8, [Tightening torque (recommended)] 25 N·m
Safety pan drain port : For Ø11 inner-diameter hose
Pump capacity
Cooling capacity